Premium VRLA Battery for Mission-Critical Applications

Leoch PLH62FT(A)

Leoch PLH62FT 62Ah front terminal battery for compact telecom backup power

Product Overview

The Leoch PLH62FT(A) is a premium 12V 62Ah Pure Lead Front Terminal VRLA battery engineered specifically for critical applications requiring exceptional reliability and performance. This maintenance-free battery delivers superior high-rate discharge capability, extended service life, and excellent deep discharge recovery in telecommunications, data centers, network equipment, and other mission-critical installations.

Buy Leoch PLH62FT(A) from Critical Power Battery Solutions

  • Leoch Authorized Distributor
  • Application-Specific Consultation
  • Competitive Leoch Volume Discounts
  • Global Leoch Shipping Capabilities
  • Leoch Warranty Processing & Support
  • Leoch Bulk Order Fulfillment
  • Emergency Delivery Options
  • Sustainable Battery Disposal Services

Leoch PLH62FT(A) Key Features & Benefits

  • Pure Lead Technology:
    99.99% pure lead plates for superior performance and extended service life
  • Front Terminal Design:
    Simplified installation and maintenance in rack-mounted applications
  • Extended Service Life:
    15+ years design life, significantly longer than standard VRLA batteries
  • Superior Cycle Performance:
    Up to 1200 cycles at 50% depth of discharge
  • Wide Temperature Range:
    Exceptional performance from -40°F to 131°F (-40°C to 55°C)
  • Low Internal Resistance:
    Higher efficiency and reduced heat generation during discharge
  • Maintenance-Free Design:
    Sealed construction eliminates the need for water additions
  • Ultra-Low Self-Discharge:
    Maintains capacity during extended storage periods
  • Non-Hazardous:
    Classified as “non-spillable” for shipping purposes
  • Environmentally Friendly:
    99% recyclable at end of service life

Leoch PLH62FT(A) Technical Specifications

Specification

  • Chemistry:
  • Design:
  • Nominal Voltage:
  • Capacity:
  • Design Life:
  • Internal Resistance:
  • Self-Discharge Rate:
  • Operating Temperature:
  • Float Voltage:
  • Cycle Use Voltage:
  • Max Charge Current:
  • Max Discharge Current:
  • Terminal Type:
  • Dimensions (L×W×H):
  • Weight:
  • Warranty:

Details

  • Valve Regulated Lead Acid (VRLA)
  • Pure Lead AGM with Front Terminal Access
  • 12V
  • 62Ah @ 10-hour rate to 1.80V per cell @ 77°F (25°C)
  • 15+ years in float service at 77°F (25°C)
  • Approx. 6.5 mΩ (fully charged @ 77°F/25°C)
  • <1% per month at 77°F (25°C)
  • -40°F to 131°F (-40°C to 55°C)
  • 13.5-13.8V @ 77°F (25°C)
  • 14.4-14.7V @ 77°F (25°C)
  • 18.6A
  • 620A (5 sec)
  • M6 Front Access Threaded Insert
  • 9.65 × 5.43 × 8.19 inches (245 × 138 × 208 mm)
  • 44.1 lbs (20 kg)
  • 3-year full replacement

  • Chemistry:
  • Design:
  • Nominal Voltage:
  • Capacity:
  • Design Life:
  • Internal Resistance:
  • Self-Discharge Rate:
  • Operating Temperature:
  • Float Voltage:
  • Cycle Use Voltage:
  • Max Charge Current:
  • Max Discharge Current:
  • Terminal Type:
  • Dimensions (L×W×H):
  • Weight:
  • Warranty:

  • Valve Regulated Lead Acid (VRLA)
  • Pure Lead AGM with Front Terminal Access
  • 12V
  • 62Ah @ 10-hour rate to 1.80V per cell @ 77°F (25°C)
  • 15+ years in float service at 77°F (25°C)
  • Approx. 6.5 mΩ (fully charged @ 77°F/25°C)
  • <1% per month at 77°F (25°C)
  • -40°F to 131°F (-40°C to 55°C)
  • 13.5-13.8V @ 77°F (25°C)
  • 14.4-14.7V @ 77°F (25°C)
  • 18.6A
  • 620A (5 sec)
  • M6 Front Access Threaded Insert
  • 9.65 × 5.43 × 8.19 inches (245 × 138 × 208 mm)
  • 44.1 lbs (20 kg)
  • 3-year full replacement

Leoch PLH62FT(A) Applications

The Leoch PLH62FT(A) is specifically designed for:

Telecommunications:

Wireless base stations, network equipment cabinets, fiber nodes

Data Centers:

Server racks, network switches, edge computing installations

UPS battery replacement systems icon for uninterruptible power supply applications

UPS Systems:

Small to medium-sized uninterruptible power supplies

Security system icon for UPS battery backup and emergency power applications

Security Systems:

Access control, surveillance equipment, alarm systems

Medical equipment icon for UPS battery backup and critical power systems

Medical Equipment:

Portable medical devices, diagnostic equipment

Industrial factory icon for battery backup and manufacturing power systems

Industrial Controls:

Process control systems, automation equipment

Renewable Energy:

Small-scale solar and wind energy storage

Leoch PLH62FT(A) Competitive Alternatives

When comparing energy storage solutions, the Leoch PLH62FT(A) offers several advantages over competing products:

  • Leoch PLH62FT(A) vs. EnerSys PowerSafe SBS 62F: Comparable performance at a more competitive price point
  • Leoch PLH62FT(A) vs. C&D Technologies TEL12-60: Enhanced high-rate discharge capability
  • Leoch PLH62FT(A) vs. CSB TPL12600: Superior deep discharge recovery and cycle life
  • Leoch PLH62FT(A) vs. Yuasa NPL65-12: Better high-temperature performance and longer design life
Leoch PLH62FT 62Ah front terminal battery for compact telecom backup power

Access comprehensive technical information for the Leoch PLH62FT(A):

Download

Product Brochure

Why Choose Critical Power Battery Solutions for Your Leoch PLH62FT(A) Needs

As an authorized reseller of Leoch batteries, Critical Power Battery Solutions offers unmatched expertise and service for Leoch PLH62FT(A) batteries:

  • Technical Expertise: Our team of battery specialists provides expert guidance for your specific application
  • Competitive Pricing: Direct distributor relationship ensures the best possible pricing
  • Worldwide Shipping: Fast, reliable delivery to any global location
  • Installation Support: Professional installation and commissioning services available
  • Warranty Administration:  Streamlined warranty processing and support
  • Recycling Services:  Environmentally responsible disposal of old batteries

Leoch PLH62FT(A) Frequently Asked Questions

Leoch PLH62FT(A) batteries are specifically engineered for telecom and data center environments with several key advantages: 1) The pure lead technology provides exceptional performance and longevity in elevated temperature environments common in these applications, 2) The front terminal design optimizes rack space utilization and simplifies maintenance, 3) The low internal resistance ensures minimal voltage drop during high-rate discharge events, and 4) The extended service life of 15+ years reduces total cost of ownership and maintenance frequency. For a detailed assessment of how PLH62FT(A) batteries can benefit your specific telecom or data center application, contact CPBS technical experts at 630-984-9718.

The pure lead technology in Leoch PLH62FT(A) batteries extends service life through several mechanisms: 1) The 99.99% pure lead plates are significantly more resistant to grid corrosion, the primary failure mechanism in VRLA batteries, 2) The absence of alloying elements eliminates the formation of harmful compounds that can accelerate aging, 3) The higher purity lead provides superior conductivity, reducing internal heat generation during charge and discharge cycles, and 4) The specialized plate design maintains structural integrity over extended periods. These factors combine to deliver a 15+ year design life, approximately 3 times longer than standard VRLA batteries. For specific lifespan projections based on your application and environment, contact CPBS at 630-984-9718.

For optimal performance and longevity of Leoch PLH62FT(A) batteries, follow these installation best practices: 1) Install in a clean, dry environment with ambient temperature as close to 77°F (25°C) as possible, 2) Maintain at least 0.5 inches (12.7mm) spacing between batteries for proper cooling, 3) Ensure rack or cabinet is properly rated for the weight load, 4) Apply anti-oxidation compound to all terminal connections, 5) Torque terminal connections to 70-85 in-lbs (7.9-9.6 N-m), 6) Verify proper float voltage settings with temperature compensation, and 7) Record baseline measurements including voltage, internal resistance, and temperature for future reference. For professional installation assistance or site-specific recommendations, contact CPBS at 630-984-9718.

Despite being maintenance-free in terms of electrolyte additions, Leoch PLH62FT(A) batteries benefit from a regular inspection and testing schedule: 1) Monthly visual inspection for physical abnormalities, 2) Quarterly voltage measurements and terminal connection checks, 3) Semi-annual internal resistance measurements to track battery health, 4) Annual capacity testing for critical applications, and 5) Continuous monitoring via battery management systems when possible. The pure lead technology significantly reduces maintenance requirements compared to standard VRLA batteries, but regular assessment helps ensure optimal performance and early detection of potential issues. For assistance developing a customized maintenance program for your PLH62FT(A) battery installation, contact CPBS at 630-984-9718.

In renewable energy applications, Leoch PLH62FT(A) batteries deliver exceptional cycle life performance: approximately 1200 cycles at 50% depth of discharge (DOD), 600 cycles at 80% DOD, and 300 cycles at 100% DOD. This performance significantly exceeds standard VRLA batteries, which typically provide 200-300 cycles at 50% DOD. The pure lead technology’s superior resistance to plate sulfation and grid corrosion enables this extended cycle life. For renewable energy systems, we recommend limiting regular discharge to 50% DOD to maximize battery lifespan. For assistance designing an optimal renewable energy storage system using PLH62FT(A) batteries, contact CPBS technical experts at 630-984-9718.

Critical Power Battery News

ISO 9001 Certified – Through Our Parent Company , ATS

Our operations are supported by ISO 9001-certified processes through Advanced Technical Services Inc.
(ATS), providing you with confidence in every order and continuous commitment to improvement.

Expert Battery Sizing When Precision Matters

Don't risk undersizing or overspending on your critical power system. Our battery sizing experts bring over four decades of experience to ensure your installation meets exact specifications for optimal performance and longevity.

Why Schedule a Battery Sizing Consultation:

Precision engineering icon for advanced battery systems and technical expertise
Precision Engineering

Get exact calculations based on your specific load requirements and runtime needs

Application-specific icon for customized battery solutions and expert sizing
Application-Specific Expertise

Benefit from specialized knowledge in telecom, data center, utility, and renewable energy applications

Cost optimization icon for battery replacement services and value engineering
Cost Optimization

Avoid unnecessary expenses from oversizing or costly downtime from undersizing

Compliance assurance icon for battery standards and regulatory requirements
Compliance Assurance

Ensure your battery system meets all relevant industry standards and regulations

Future-proofing icon for UPS battery solutions and technology advancement
Future-Proofing

Plan for growth with scalable solutions that accommodate your evolving power needs

Our battery sizing experts will analyze your critical load requirements, environmental conditions, and backup duration needs to recommend the perfect solution for your application.

DELIVERABLE – IEEE 485 Battery Sizing report as well as a detailed pricing quote.

Free Battery Sizing Consultation